Industrial Valve Installation: Critical Don’ts and Correct Practices
2026-11-13
Valve installation may seem simple, but in reality, any negligence in details can easily lead to problems.
Taboo 1: Not conducting a visual inspection before installation
Consequences: The valve body exhibits sand holes and cracks, and the flange was misaligned during transportation, leading to leakage upon direct installation.
Correct practice: Inspect the valve casing one by one before installation, verifying the model, pressure rating, and material.
Taboo 2: Not cleaning the valve
Consequences: Residual casting sand, grease, or debris trapped between valve discs can enter the pipeline, causing damage to the pump body or blocking the instrument.
Correct practice: Before installation, remove the rust-preventative oil and dirt from the sealing surface of the valve port (unless there are special lubrication requirements in the design).
Taboo 3: Uneven stress distribution during tightening of flange bolts
Consequence: The flange is subjected to unilateral stress, resulting in misalignment of the gasket or fracture of the flange.
Correct approach: Symmetrical, uniform, and tightened in multiple stages.
Taboo 4: Installing without considering the flow direction of the medium
Consequences: For globe valves and check valves, installing them upside down can lead to significant flow resistance, and a malfunctioning check valve can result in water hammer.
Correct practice: Strictly adhere to the direction indicated by the arrow on the valve body Taboo 5: Ignoring the installation environment space
Consequence: The valve handwheel is pressed against the wall, making it impossible to fully open or close; there is no space to tighten the flange bolts.
Correct approach: Reserve sufficient space for operation and maintenance.
Taboo 6: Forcing a match
Consequence: Misalignment of the pipeline, forced connection with a valve, resulting in the valve body bearing pipeline stress and the shell cracking.
Correct approach: Precise pipeline prefabrication is essential, and the pipelines on both ends of the valve should align naturally.
Taboo 7: Improper selection of gaskets or reuse of old gaskets
Consequence: Gasket failure under high temperature and high pressure, or corrosion medium penetrating through the gasket.
Correct approach: Select the appropriate gasket based on the medium and temperature, and replace the gasket with a new one after cleaning the flange sealing surface.
Taboo 8: No degreasing treatment for cryogenic valves
Consequences: Under oxygen-rich or low temperature conditions, oil contamination may spontaneously ignite or freeze, causing the valve to jam.
Correct practice: The oxygen pipeline and cryogenic valves must be strictly degreased.
Taboo 9: The installation location places the operator in a dangerous area
Consequences: The steam valve outlet is facing the operating aisle; there is no operating platform for the high-altitude valve.
Correct practice: The direction of the handwheel should be convenient for operation, avoiding directing the splashing of high-temperature medium towards the sidewalk.
Taboo 10: The discharge port of the safety valve faces the sidewalk or equipment
Consequence: Injury caused by the ejection of high-temperature and high-pressure medium during takeoff.
Correct practice: The safety discharge outlet should be led to a safe location. Taboo 11: Using a handwheel or handle as a lifting point
Consequences: Deformation of the handwheel, bending of the valve stem, and packing leakage.
Correct method: When lifting, the valve body or flange neck should be bundled.
Taboo 12: Valves are left in a slightly open state all year round (except for regulating valves)
Consequence: The medium erodes the sealing surface over a long period of time, causing damage and resulting in a leaky seal when closed.
Correct practice: Gate valves and globe valves should either be fully opened or fully closed (regulating valves are required for regulating conditions).
Taboo 13: No switch markings for rising stem gate valves
Consequence: It is difficult to determine the actual position of the valve plate based on the position of the valve stem, especially for buried or overhead valves.
Correct practice: Make good marks for opening/closing limits.
Taboo 14: Working outdoors for extended periods without proper protection
Consequences: Rusted valve stem threads, aged packing, and frozen and cracked valve body due to water accumulation in winter.
Correct practice: Important valves should be equipped with rain covers, and the valve stems should be regularly lubricated.